We use cookies on our website to ensure we provide you with the best experience on our website. By using our website, you agree to the use of cookies for analytics and personalized content.This website uses cookies. More Information
It seems like your browser didn't download the required fonts. Please revise your security settings and try again.
Reference / FAQ

What are the heat dissipation / BTU specifications for Barracuda Network Products?

  • Type: Knowledgebase
  • Date changed: 2 years ago

Solution #00003966

Scope:

All Barracuda products, all firmware versions.

Answer:
The heat dissipation specifications, expressed in BTU per hour, for Barracuda Networks products are as follows:

 

Barracuda Spam Firewall

  • Model 100 / 200:    375 BTU/hr
  • Model 300:              450 BTU/hr
  • Model 400:              525 BTU/hr
  • Model 600:              676 BTU/hr
  • Model 800:            1539 BTU/hr
  • Model 900:            2027 BTU/hr
  • Model 1000:          2702 BTU/hr


Barracuda Link Balancer and Load Balancer

  • Model 230 / 240:     375 BTU/hr
  • Model 330 / 340:     450 BTU/hr
  • Model 430 / 440:     525 BTU/hr
  • Model 640:               676 BTU/hr

Barracuda Message Archiver

  • Model 350 / 450:     676 BTU/hr
  • Model 650:             1539 BTU/hr
  • Model 850 / 950:   1914 BTU/hr 

Barracuda Web Application Firewall

  • Model 360:               450 BTU/hr
  • Model 460:               526 BTU/hr
  • Model 660:               676 BTU/hr

 Barracuda Web Filter and IM Firewall

  • Model 210 / 220:     375 BTU/hr
  • Model 310 / 320:     450 BTU/hr
  • Model 410 / 420:     525 BTU/hr
  • Model 610 / 620:     676 BTU/hr
  • Model 810:             1539 BTU/hr
  • Model 910:             2027 BTU/hr
  • Model 1010:           2702 BTU/hr

Barracuda Backup Appliance:

  • Model 190: 143 BTU/hr
  • Model 290: 102 BTU/hr
  • Model 390: 307 BTU/hr
  • Model 490: 307 BTU/hr
  • Model 690: 778 BTU/hr
  • Model 890 / 891 / 892: 1638 BTU/hr
  • Model 990 / 991: 2825 BTU/hr
  • Model 995 / 995A: 3194 BTU/hr
  • Model 1090 / 1091: 3439 BTU/hr

Note:

It may be necessary to calculate the Wattage and BTU output of the Barracuda Spam Firewall.

Terms:
Watts - It measures a rate of energy conversion.
BTU - A BTU, short for British Thermal Unit, is a basic measure of thermal (heat) energy.
Steps for Calculating:

1. Get the datasheet from Barracuda Website, found here: http://www.barracudanetworks.com/ns/products/spam_specs.php
2. To get wattage, multiply AC Input Current (amp) by 120Vac.
For example, model 800 is 4.1 amps 120 x 4.1 = 492 watts
3. To get BTU, multiply wattage by 3.412.
For example, 492 x 3.412 = 1679 BTU 4. AC systems are often rated in "tons."
4. To get the number of tons needed to cool a box, divide BTUs by 12,000.
For example: 1679 / 12000 = 0.14 tons of AC capacity.


List by Mode Number:
 
 

Model           AMPS            WATTS           BTU

 100                1                    120               409

 200                1                    120               409

 300                1.2                 144               491

 400                1.4                 168               573

 600                1.8                 216               736

 800                4.1                 492              1678

 900                5.4                 648              2210

1000               7.2                 864              2947


Link to This Page: